TTR20变比测试仪商品简介:



range of10,000:1

TTR20变比测试仪详细信息:



  • Fast, easy h-held operation. No need to kneel or bend down to operate the instrument.
  • Powered by six stard “AA” alkaline batteries; no ger needed. Provides up to 12 hours of field operation.
  • Measures turns ratio range of 10,000:1, with a high accuracy (±0.1%, 0.8 to 2000) at a low excitation voltage.
  • Records ratio errors for bushing CTs to an accuracy of ±0.1% nameplate. This reduces the need for additional test equipment improves set-up time.
  • Perfect for meter shops, the TTR20 can be used for inspection purposes to determine the no-load accuracy of most CTs PTs. It also can be used to determine the need to test potentially faulty CTs PTs.
  • Automatic self-calibration for each test.
Included Accessories:
  • 1 - 35938 Combined test leads, "X/H" winding, 1.8 m (6 ft)
  • 1 - AVTMTTR20 Instruction manual



  Description

The Megger TTR20 is an automatic h-held battery operated transformer turns ratio test set. It is used to measure the turns ratio, excitation current polarity of windings in single- three-phase distribution power transformers (tested phase by phase), potential & current transformers, tapped transformers.

The unique design of the TTR20 allows the user to operate the test set while holding it in one h. It effectively eliminates the user from having to kneel or bend down to operate the instrument speeds up testing time. Realizing the extreme environments in which the TTR20 must operate, special attention has been paid to making it extra rugged, with a high impact, shock resistant case, yet incredibly lightweight at a mere 870 g (1.9 lbs).

Its design makes this instrument well suited for use in a variety of harsh environments. The TTR20 is particularly suited for testing in substations, transformer-manufacturing environments, meter shops. It features a high-contrast, backlit LCD screen which can be seen in bright or ambient light.

This unit measures a high turns ratio of 10,000:1 accurately with the lowest excitation voltage. The excellent repeatability of the TTR20 helps the users to determine the condition of transformers under test. It is designed for simple, one button operation with the measured results displayed directly on the easy to read LCD or printed to the optional printer. The TTR20 needs no additional software comes ready to use complete out of the box.

APPLICATIONS
The proper operation of a transformer relies almost entirely on the electrical properties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. A TTR is an extremely useful instrument for testing transformer windings because it can help locate several types of problems within single- three-phase transformers.

It it used to determine the no-load accuracy of CTs PTs also determine the need to further test faulty CTs PTs. The TTR20 applies voltage to the high-voltage winding of a transformer accurately measures the resulting voltage from the low voltage winding. The ratio of voltages is directly proportional to turns ratio. In addition, the unit measures excitation current polarity.

TRANSFORMER TURNS RATIO
A Transformer Turns Ratio Test Set such as the TTR20 can directly measure the turns ratio of single-phase transformers as well as three-phase transformers. Deviations in these measurements will quickly indicate problems in transformer windings in the magnetic core circuits. Transformer ratio can change due to several factors, including physical damage from faults, deteriorated insulation, contamination shipping damage. If a transformer ratio deviates more than 0.5 percent from the rated voltage ratio, it may not operate reliably. To measure small ratio changes such as this, the accuracy of a Megger TTR20 is needed.

Transformer Polarity
Polarity of a distribution transformer becomes of interest in order to determine its proper connection within a power network. The Megger TTR20 will identify normal (in phase) reverse polarity of the single-phase transformers.

Type of Power Six stard “AA” (IEC LR-6) alkaline batteries
Battery Life 12 hours of field operation
Excitation Voltage 8 V rms for testing distribution or power transformers PTs
0.5, 1.5, or 8 V ac rms for testing CTs.
The excitation voltage is switched automatically if excitation current exceeds a preset value.
Test Frequency 55 Hz internally generated providing a universal 50/60 Hz test set
Excitation Current Range 0 to 100 mA, 4-digit resolution
Turns Ratio Range 0.8 to 10,000, 5 digit resolution
Transformer Polarity Normal or reversed
Current (rms) accuracy (2% of reading + 1 digit)
Turns Ratio Accuracy 0.1% (0.8 to 2000)
0.15% (2001 to 4000)
0.25% (4001 to 10,000)
Display full graphics LCD module
adjustable back-lighting
wide temperature range
128 x 64 dots (21 acters by 8 lines)
Transformer Winding Phase Relationship ANSI C57.12.70-1978
Safety/EMC/Vibration Meets the requirements of IEC-1010-1, CE ASTM D999.75
Temperature Range Operating: -20º C to 55º C (-5º F to 130º F)
Storage: -50º C to 60º C (-55º F to 140º F)
Relative huity Operating: 0 to 90% noncondensing
Storage: 0 to 95% noncondensing
Protective Devices High voltage side shorting relay, transient voltage suppressors gas surge voltage protectors
Measuring Time Less than 5 seconds
Measurement Method ANSI/IEEE C57.12.90
Dimensions 240 H x 115 W x 50 D mm
(9.5 H x 4.5 W x 1.9 D in.)
Weight Approximately 1.3 kg (2.8 lb), including leads


TTR20变比测试仪相关产品:



TTR20变比测试仪全国售后维修

代理商售后维修区域:北京-上海-浙江-广东-河南-杭州-郑州-广州-深圳-佛山-惠州-厦门-汕头-台湾-香港-天津-西安-宝鸡-杭州-温州-常州-无锡-苏州-南京-镇江-扬州-南通-合肥-徐州-常熟-石家庄-太原-呼和浩特-沈阳-长春-哈尔滨-南京-合肥-福州-南昌-济南-郑州-武汉-长沙-广州-南宁-海口-成都-贵阳-昆明-拉萨-西安-兰州-西宁-银川-乌鲁木齐-杭州-沈阳-长春-哈尔滨-济南-武汉-广州-南宁-成都-西安-大连-宁波-厦门-青岛-深圳-杭州-淮安-连云港-昆山-嘉兴-湖州-秦皇岛-邯郸-邢台-保定-张家口-承德-廊坊-呼和浩特-包头-鞍山-大庆-锦州-铁岭-盘锦-湛江-萧山-辽宁-淄博-宁夏-绵阳-云南-朝阳-陕西-青海-北海-唐山-吉林-苏州-昆山-无锡-镇江-常州-连云港-淮安-淮阴-盐城-扬州-徐州-宜兴-江阴-南通-扬州-上海-滁州-内蒙古-新疆有销售.北京亦庄开发区,天津滨海开发区,秦皇岛经济开发区,太原经济开发区,呼和浩特经济开发区,沈阳经济开发区,营口经济开发区,大连经济开发区,长春经济开发区,哈尔滨经济开发区,虹桥经济开发区,漕河泾开发区,连云港开发区,南通开发区,昆山开发区,南京开发区,杭州开发区,萧山开发区,温州开发区,宁波开发区,芜湖开发区,合肥开发区,福州开发区,福清融侨开发区,东山开发区,南昌开发区,威海开发区,烟台开发区,青岛开发区,郑州开发区,武汉开发区,长沙开发区,萝岗区开发区,广州南沙开发区,惠州大亚湾开发区,湛江开发区,南宁开发区,重庆开发区,成都开发区,贵阳开发区,昆明开发区,拉萨开发区,西安开发区,兰州开发区,西宁开发区,银川开发区,乌鲁木齐开发区,石河子开发区,金桥出口加工区,苏州工业园,宁波大榭开发区,厦门海沧投资区,海南洋浦开发区。